BS EN 1154:1997
Building hardware Controlled door closing devices Requirements and test methods
Classifies door closers using a 6 digit coding system.
Each digit refers to a particular feature of the product measured against the standard's performance requirements.
- Digit 1 - Category of use
- grade 3: For closing doors from at least 105° open. - grade 4: For closing doors from 180° open.
- Digit 2 - Number of test cycles
- grade 8: 500 000 cycles.
- Digit 3 - Test door mass/size
Seven test door mass grades and related door closer power sizes are identified.
|
Closer Power Size |
|
|
|
1 |
|
|
|
2 |
|
|
|
3 |
|
|
|
4 |
|
|
|
5 |
|
|
|
6 |
|
|
|
7 |
|
|
- Digit 4 - Fire behaviour
- grade 0: Not suitable for use on fire/smoke door assemblies. - grade 1: Suitable for use on fire/smoke door assemblies, subject to satisfactory assessment of the contribution of the door closer to the fire resistance of specified fire/smoke assemblies. This is assessed outside of BS EN 1154.
- Digit 5 - Safety
Grade 1: All door closer devices are required to satisfy the essential requirement of safety in use.
- Digit 6 - Corrosion resistance
- grade 0: No defined corrosion resistance. - grade 1: Mild resistance. - grade 2: Moderate resistance. - grade 3: High resistance. - grade 4: Very high resistance.
The following marking denotes a closer capable of opening to 180, with a range of power sizes from size 3 to size 6, suitable for fire door use with high corrosion resistance.
|